<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://wiki.darkan.org/index.php?action=history&amp;feed=atom&amp;title=Update%3ASF_servers_back_online</id>
	<title>Update:SF servers back online - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://wiki.darkan.org/index.php?action=history&amp;feed=atom&amp;title=Update%3ASF_servers_back_online"/>
	<link rel="alternate" type="text/html" href="https://wiki.darkan.org/index.php?title=Update:SF_servers_back_online&amp;action=history"/>
	<updated>2026-07-17T21:12:25Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.46.0</generator>
	<entry>
		<id>https://wiki.darkan.org/index.php?title=Update:SF_servers_back_online&amp;diff=31910&amp;oldid=prev</id>
		<title>imported&gt;Evilbot: Category fixes</title>
		<link rel="alternate" type="text/html" href="https://wiki.darkan.org/index.php?title=Update:SF_servers_back_online&amp;diff=31910&amp;oldid=prev"/>
		<updated>2010-12-01T21:16:23Z</updated>

		<summary type="html">&lt;p&gt;Category fixes&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{{update|date=25 August 2003}}&lt;br /&gt;
&lt;br /&gt;
I apologise for the problems with the San-Franciso servers today. The problem has now been fixed and the servers should be functioning normally again.&lt;br /&gt;
&lt;br /&gt;
The following is an overview of events leading to the outage and subsequent restoration.&lt;br /&gt;
&lt;br /&gt;
# On August 24, 2003 at approximately 1:30 PM PG&amp;amp;E experienced a power failure on the lines servicing the San Franciso hosting facilitiy&lt;br /&gt;
# At this time the facility went on UPS Power and then subsequently generator backup without incident.&lt;br /&gt;
# This backup continued to run until August 25, 2003 at 2:47 AM when a component in the generator itself failed. The component that failed is known as a CT and monitors power within the generator. Due to a manufacturers design problem, the CT was not physically restrained to prevent possible movement within the generator.&lt;br /&gt;
# At some point after running for 14 plus hours the CT physically spun inside the generator causing a physical short between two of the electrical phases, which in-turn caused several of the control boards to fail. With built in safeties, the generator shut itself down.&lt;br /&gt;
# The Building Engineering staff was notified that the generator failed and they started repair efforts. The generator technicians were called and dispatched to the facility.&lt;br /&gt;
# At 7:30 AM PG&amp;amp;E dispatched a truck to reconnect the facility to the power grid.&lt;br /&gt;
# At 8:03 AM PG&amp;amp;E reconnected the power grid and power was restored. &lt;br /&gt;